AI data center cabinet power surges into the hundreds of kilowatts: The flow and heat transfer challenges of liquid cooling and immersion cooling can no longer be addressed with empirical formulas alone.
Release time:
2026-10-22 11:29
Source:
AI data centers are pushing cabinet power levels from 5–10 kW all the way up into the triple digits. Traditional approaches—empirical formulas and “oversizing based on experience”—begin to break down at this scale: where hotspots occur, where hot air recirculates, and how bubbles behave in immersion tanks have all become issues that must be carefully analyzed. This paper dissects this heat‑transfer chain by examining nine publications from 2025–2026.
01 Flow and Heat Transfer in Liquid Cooling and Immersion Cooling
WHEN AIR RUNS OUT
Rising power density has shifted the challenge. A sensitivity analysis of cooling architectures for AI data centers shows that cabinet power densities have climbed from the traditional 5–10 kW range into the 30–100 kW range. Surveyed peak loads for HPC and AI workloads reached 44 kW, and some AI deployments exhibit thermal densities above 120 kW (for example, 160 kW). For the latest-generation AI cabinets that can still be air-cooled, the performance gap between air cooling and liquid cooling is roughly 50%. [1] 。

Figure 1: Rack power distribution for general workloads and HPC/AI workloads: AI workload peaks are concentrated in the 16–20 kW range (reproduced from reference [1]).
The challenges are continuing to shift from the cabinet level down to the chip scale. A review of 2.5D/3D heterogeneous integration notes that the average thermal flux in actual packaging has consistently exceeded 100 W/cm², with local hotspots reaching or even surpassing 1 kW/cm²; at power levels of 600–700 W, interposer hotspot temperatures can exceed 120°C, air cooling for 2.5D stacks reaches its limits at around 300 W, and liquid or hybrid cooling becomes necessary for 3D stacks at approximately 350 W. [2] 。

Figure 2: Proportion of AI cabinets categorized by liquid-cooling suitability: The largest customer base (approximately 40%) falls into the 40–59% suitability bracket (reproduced from reference [1]).
Policy measures are also tightening. Several provinces and cities in China have mandated that the design PUE of new data centers not exceed 1.2; the “East Data, West Computing” initiative specifies a PUE below 1.25 for eastern hub nodes and below 1.2 for western ones. Meanwhile, the optimal PUE for air-cooling systems is around 1.25—single-phase immersion cooling has been assessed as a technological approach capable of bringing PUE close to its theoretical limit. [3] . Macro-level pressures are also mounting: data centers account for about 1.5% of global electricity consumption, a figure projected to rise by roughly 160% by 2030, with approximately 40% of that energy devoted to cooling. [4] 。
Taken together, these three sets of figures make one thing clear: liquid cooling and immersion cooling are not merely “more advanced options”; they are the only cooling pathways that still have room for further improvement. Moreover, the fundamental physical mechanisms underlying these two approaches—forced convection, boiling phase change, and gas–liquid interface dynamics—are precisely the aspects that empirical formulas struggle most to capture.
02 CFD Foresees Hotspots and Backflow in Advance
SEE IT BEFORE IT HAPPENS
Cabinet-level issues include hotspots and bypass flows. Research indicates that CFD models can provide detailed analysis of airflow and thermal patterns within data centers, capturing Hot Reflux Zone and Cool Gas Bypass These are the adverse effects that reduce efficiency and increase energy consumption; the multi-region conjugate heat transfer (CHT) method is precisely a well-established tool for conducting such analyses. [5] The hot spot locations, recirculation paths, and the degree of mixing between hot and cold aisles can all be calculated during the design phase, eliminating the need to rely on trial-and-error after equipment is powered on.

Figure 3: Rack-level CFD modeling: geometry, measurement points, and in-rack layout are all incorporated into the model (reproduced from reference [5]).
Measured operational data corroborates just how significant the hidden costs can be. A system equipped with a distributed sensor array and LSTM-based predictive control reduced the cumulative duration of hotspots (at a threshold of 27°C) from 48 hours to 2 hours—a reduction of nearly 96%—while cutting cooling energy consumption by 37.5% and lowering the PUE from 1.48 to 1.30. [6] It is worth noting that these gains come from “detecting and intervening” in hotspots that have already formed—whereas the goal of CFD during the design phase is to prevent hotspots from occurring in the first place.

Figure 4: Runtime architecture of sensor array + LSTM predictive control: CFD addresses the other end of the same problem during the design phase (adapted from reference [6]).
The two approaches are complementary rather than mutually exclusive: CFD handles the most costly design decisions—such as cabinet layout, cold‑aisle containment, and liquid‑cooling plate flow paths—at the schematic stage, while sensing and predictive control manage load drift during operation. Without the former, the latter would constantly be left to clean up the mess.
03 FlowVision Solution
ONE SOLVER FOR THE WHOLE CHAIN
From the computer room to the immersion tank, FlowVision Cover with the same set of solvers: Heat Transfer and Fluid–Structure Conjugate Heat Transfer (CHT) Directly couple the solid wall with the cooling fluid, and design the server cabinet layout and cold plate flow channels. Multiphase Flow Model at the Gas–Liquid Interface Handles single-phase/two-phase working fluid flow in immersion cooling. Automatically generates orthogonal grids based on the true geometry and adaptively refines them, eliminating the need to simplify real assemblies such as cabinets, servers, and cold plates before simulation.

Figure 5: Single-phase immersion cooling system: The coolant—circulation pump—heat exchanger—cooling water side form a complete loop (reproduced from reference [3]).
Two-phase immersion is the next-generation approach and represents the most demanding scenario in terms of flow details. A review of two-phase thermosiphon cooling systems compares the circulation behavior of various working fluids under different pressures and fill ratios. [7] ; On the boiling side, the ultrasonic enhancement experiment measured a maximum heat transfer coefficient of 31.0 kW/m², and the underlying mechanism lies precisely in the details of bubble detachment and fluid mixing. [8] ; Synthetic jet research suggests that, during the suction phase, backflow of heated fluid can occur locally deterioration Heat exchange [9] —These direction-dependent details cannot be resolved through empirical correlations.
The International Energy Agency projects that data center electricity consumption will reach 945 TWh by 2030. [7] Power is still increasing, leaving little room for empirical correlations—only narrowing. Entrusting flow and heat transfer problems to validated numerical simulations is one of the few approaches that remains viable at this scale.
Once cabinet power exceeds one hundred kilowatts, the critical factor in thermal design is no longer how much experience one has, but whether the calculations can be done accurately.
References
[1] Sensitivity analysis of liquid-to-air and liquid-to-liquid cooling metrics under multilayer AI workload conditions. Discover Networks, 2026. DOI:10.1007/s44354-026-00035-0
[2] Thermal Management Challenges in 2.5D and 3D Chiplet Integration: A Review on Architecture–Co-Design. Eng — Advances in Engineering, 2025. DOI:10.3390/eng6120373
[3] Overview of Single-phase Immersion Liquid Cooling Technology. International Journal of Energy, 2025. DOI:10.54097/dhmrxm38
[4] Convective heat transfer optimization for liquid cooling plates driven by field synergy. Energy, 2026. DOI:10.1016/j.energy.2026.142364
[5] Maximizing waste heat recovery from a building-integrated edge data center. Scientific Reports, 2025. DOI:10.1038/s41598-025-22498-x
[6] Proactive Cooling Control Algorithm for Data Centers Based on LSTM-Driven Predictive Thermal Management. Applied System Innovation, 2026. DOI:10.3390/asi9010021
[7] Two-phase thermosiphon cooling in data centers: a comprehensive review of refrigerants. Journal of Engineering and Applied Science, 2025. DOI:10.1186/s44147-025-00833-3
[8] The effect of ultrasound manipulation on boiling performance during immersion cooling. Journal of Thermal Analysis and Calorimetry, 2025. DOI:10.1007/s10973-025-14458-4
[9] Heat Transfer Enhancement in Immersion Cooling by Liquid Synthetic Jet. ICTEA, 2026. DOI:10.54097/vhc1dw52
FlowVision fluid simulation software,AI Data Center,Hotspots and Backflow,Thermal stratification,Heat Transfer / Conjugate Heat Transfer,Multiphase Flow Model at Liquid Interfaces